VA to Amps Calculator
Convert apparent power in volt-amps (VA) to current in amps (A). Select single phase or three phase, enter the apparent power in volt-amps and the line-to-line voltage in volts, and press Calculate to get amps. Everything runs locally in your browser.
Choose the phase
Pick "Single phase" for a one-phase load or "Three phase" for a three-phase system. The formula hint under the selector switches to match, and the voltage field always expects the line-to-line voltage.
Enter volt-amps and volts
Type the apparent power in volt-amps (VA) and the voltage in volts (V). Zero VA is allowed and simply gives 0 A, but the voltage must be greater than zero — amps are a quotient, so dividing by 0 volts is undefined. Negative values are rejected.
Press Calculate, read amps
The result appears in amps (A), rounded to at most three decimals. Press Reset at any time to clear the fields and start over.
VA to amps calculation
- How do you convert VA to amps for single phase?
- The current I in amps (A) is equal to the apparent power S in volt-amps (VA), divided by the voltage V in volts (V): I(A) = S(VA) / V(V). For example, a 1200 VA load on a 120 V supply draws 1200 / 120 = 10 A.
- How do you convert VA to amps for three phase?
- The current I in amps is equal to the apparent power S in volt-amps, divided by the square root of 3 times the line-to-line voltage VL-L in volts: I(A) = S(VA) / (√3 × VL-L(V)). For example, 10000 VA on a 400 V line-to-line supply gives 10000 / (√3 × 400) ≈ 14.434 A. Using line-to-neutral voltage instead, the equivalent form is I(A) = S(VA) / (3 × VL-N(V)).
- Why is the three-phase current lower than single phase for the same VA and volts?
- A three-phase system delivers power over three conductors, so each conductor carries only 1/√3 (about 58%) of the current the same apparent power would draw from a single-phase supply at the same voltage. The calculator applies the √3 divisor automatically when you pick "Three phase".
- Which voltage goes in the volts field?
- Always the line-to-line voltage: the supply voltage measured between conductors (120 V or 230 V mains for single phase, 208 V, 400 V or 480 V for typical three-phase systems).
- Worked example
- A 5000 VA three-phase load on a 208 V line-to-line supply draws I = 5000 / (√3 × 208) ≈ 13.879 A. The same 5000 VA on a single-phase 208 V supply would draw 5000 / 208 ≈ 24.038 A. Note VA to amps needs only VA and volts; converting from watts instead requires the power factor.